Start Up Control System Gas Turbine

Start Up Control System Gas Turbine Points : Start Up Control System Gas Turbine Power Plant The startup control system coordinates the control of fuel flow during startup. The start-up control interacts with the sped control system and temperature control system as necessary to ensure successfully firing, proper turbine speed, while limiting the rate of temperature rise and acceleration to protect the turbine. Both the startup control and the speed control overridden by the temperature control system when the prevailing turbine temperature warrants the control of temperature rather than speed or pre-set fuel limits. Pre-set fuel limits, controlled solely by the startup control are: firing, fuel warm-up fuel, and the maximum called for fuel during acceleration.

No comments: