Practical Absorption System
Practical Absorption System
Points : Practical Absorption System, Heat Exchanger, Analyzer, Rectifier
The simple absorption system discussed above can function and provide refrigeration
but its operating efficiency will be very low. In order to make it more practical it is
fitted with a heat exchanger, an analyzer and a rectifier. These accessories which help
to improve the performance and working of the plant are described below.
1. Heat Exchanger
The location of the heat exchanger between the generator and absorbers is ideal. The
strong solution pumped from the absorber to the generator must be heated; and the
weak solution from the generator to the absorber must be cooled. The heat exchanger
between the two streams, therefore, reduce both the cost of heating the generator
and the cost of cooling the absorber.
2. Analyzer
The analyzer is a direct contact heat exchanger consisting of series of tray mounted
above the generator. Its function is to remove partly some of the unwanted water
particle associated with ammonia vapour going to the condenser The water vapours if
allowed to enter the condenser may enter the expansion valve Where they will freeze
and choke the pipe line.
3. Rectifier
The final reduction (elimination) of the percentage of water vapour occurs in the
rectifier a water cooled heat exchanger which condenses water vapour (and some
ammonia) ad returns it to the generators. The net refrigerating effect of such a
machine is the heat extracted in the evaporator. The total energy supplied for
operating the machine is the sum of the work done by the liquid pump and the heat
supplied in the generator.