Simple Absorption System
Points : Simple Absorption System
If the compressor in a vapour compression system were replaced with a generator is
absorber assembly the result would be a simple absorption system.
In this case the low pressure refrigerant vapour (Ammonia) coming from the
evaporator is absorbed in the absorber by the weak solution of refrigerant water.
Absorption of ammonia lowers the pressure in the absorber, which in turn thaws more
ammonia vapour from the evaporator. Some form of cooling arrangement usually
water cooling, is employed in the absorber to remove the heat of solution evolved
there. This is necessary to increase the absorption capacity of water because at high
temperature, water absorbs less ammonia. The solution in the absorber is called a
strong solution because it is rich in refrigerant. The pump draws strong solution from
the absorbers, builds up a pressure up to 10 Kgf/cm2 and forces the
strong solution in the generator.
In the generator the strong solution of ammonia is heated by some external source
such as gas or steam In the heating process the ammonia vapour I driven out of the
solution as a high pressure vapour leaving behind in the generator a weak solution.
The weak solution flows back to the absorber through a restriction which maintains
the pressure differential between the high and low sides of the system. From the
generator the refrigerant vapour is conducted to the condenser where it is condensed.
Then the high pressure liquid ammonia is passed through a throttle valve to the
evaporator where it absorbs its latent heat thus producing cold.